Fire Hydrant Testing Machine

The Fire Hydrant Testing Machine is built for pressure and burst testing of firefighting equipment. Configured here as air consumption: 1.6 Nm³/min. The test sequence is stored as a recipe, so one bench can serve several cylinder sizes and markets.

Send Inquiry

Description

1. Application Scope

The fire hydrant test machine developed by Jinan Bonor Machinery Co., Ltd. is specially designed for hydrostatic pressure testing of fire hydrants. It is widely used in manufacturing factories, quality inspection institutes, scientific research institutions and universities for production inspection and R&D of various fire valve products.

The machine complies with the following standards:

  • GB3445-2005 Indoor Fire Hydrant
  • GB4452 General Technical Requirements for Outdoor Fire Hydrants
  • 2-2006 Fire Couplings
  • GB8181-2005 Fire Water Performance

Controlled by computer, the unit automatically runs tests and records data to ensure high test accuracy. System pressure, flow rate and other parameters can be adjusted automatically.

2. Control System

The control system adopts a two-level architecture consisting of upper computer and lower computer:

  • Upper computer: Handles graphic display, data calculation and data management with independent control modules for modularized operation;
  • Lower computer: Executes commands from the upper computer to regulate the hydraulic system to target pressure. It features high pressure control accuracy, excellent pressure holding performance and automatic real-time pressure compensation.

Functions including automatic data saving upon power failure and test resumption after power restoration ensure uninterrupted testing.

3. Equipment Features

  1. Equipped with imported pneumatic gas booster pump for adjustable and controllable output pressure;
  2. Advanced technology and compact structural design, small footprint, light weight and nice appearance;
  3. All pressure-bearing components adopt world-famous brand standard parts without welded joints, which enables easy disassembly, high safety factor, long service life and convenient maintenance;
  4. Built-in water circulation system allows fast sample loading/unloading. Multi-sample simultaneous testing improves the automation efficiency of hydrant port pressure tests.

4. Technical Parameters

  1. Driving air pressure: 0.1–0.69 MPa, output pressure is proportional to driving air pressure
  2. Air consumption: 1.6 Nm³/min
  3. Test pressure range: 0–20 MPa (customizable based on customer requirements)
  4. Test medium: Water
  5. Custom Bonor data acquisition software is available as an optional item

Applications of the firefighting equipment test bench

The fire protection market is inspected closely, so the test bench has to do two jobs at once: prove the hardware, and produce a certificate that survives an audit. The Fire Hydrant Testing Machine is specified around both.

  • Extinguisher refilling and service stations — periodic requalification of cylinders before recharge, with the test date recorded on the unit.
  • Valve and coupling production — body strength and seat tightness on extinguisher valves and hose couplings.
  • Municipal and industrial fire brigades — in-house periodic testing of the equipment they carry.

What to specify before we build yours

  • Standard and test sequence — EN 3, GB 4351, GB/T 9251 or the local code, including the hold times and the deformation limit.
  • Cylinder sizes and volumes — from 1 kg portable bodies to wheeled and fixed units; the jacket and the clamp follow the size range.
  • Medium and drying — water is standard, but the bodies must be dried afterwards, so a drying stage is often part of the same cell.
  • Certificate format — the fields your inspector expects: serial number, test pressure, hold time, deformation, operator and date.

Currently configured as: Air consumption: 1.6 Nm³/min. Other ranges and fixtures are built to order.

How to choose a firefighting equipment test bench

Firefighting testing is a volume business, so cycle time and record quality matter as much as pressure accuracy:

  • Count the steps around the test. Filling, venting, drying and marking often take longer than the pressure hold itself. A bench that integrates them changes the throughput of the whole line, not just the test station.
  • Confirm the deformation measurement method. Water-jacket and weighing methods are both accepted by different codes; the one your certificate has to show determines the fixture.
  • Plan for different cylinder sizes. Interchangeable clamps and jacket inserts are much cheaper than a second bench, but only if they are designed in from the start.

Frequently asked questions

Which standards can the test sequence follow?

The common ones are EN 3 for portable extinguishers, GB 4351 for Chinese-made bodies and GB/T 9251 for hydrostatic test methods, and the bench program is written to whichever of these your market requires. If you export to several markets, the sequence is stored as a recipe and selected per batch.

Does the machine test burst strength as well as proof pressure?

Yes — proof pressure and burst are the same pressure circuit with different set points and different acceptance criteria. A burst test is destructive, so it is normally run on samples rather than on every unit.

How long does one complete test cycle take?

A single-body proof test including fill, hold, drain and record typically takes a few minutes; the exact figure depends on body volume, fill rate and the hold time your standard requires. We quote cycle time for your specific body size rather than an average.

Related equipment and further reading

Need a pressure range, fixture or test standard that is not listed here? Send the specimen list and the standard you test to and we will come back with a configuration and a price within one working day.

Leave Us a Message

Have questions about this product? Fill in the form below and we will reply by email.

Go to Top